Table ED-2 — Electrical Characteristics — Power Exhaust Accessory

Accessory
Operating

Amps

Tons

Voltage

Phase

HP

RPM

FLA

LRA

208-230

1

3/4

1040

6.6

13.5

460

1

3/4

1040

3.2

8.4

575

1

3/4

1040

2.1

5.2

Table ED-1 — Unit Wiring

Standard Indoor Fan Motor

Oversize Indoor Fan Motor

Unit

Minimum

Maximum Fuse Size

Minimum

Maximum Fuse Size

Unit

Operating

Circuit

or Maximum

Circuit

or Maximum

Tons

Model No.

Voltage Range

Ampacity

Circuit Breaker

1

Ampacity

Circuit Breaker

1

WC*150B3

187-253

66.0

80

72.0

80

12½

WC

*

150B4

414-506

31.0

40

34.0

40

WC

*

150BW

517-633

25.0

30

28.0

35

WC

*

180B3

187-253

76.0

90

82.0

100

15

WC

*

180B4

414-506

39.0

45

42.0

50

WC

*

180BW

517-633

31.0

35

33.0

40

WC

*

240B3

187-253

96.0

125

103.0

125

20

WC

*

240B4

414-506

49.0

60

53.0

60

WC

*

240BW

517-633

38.0

45

41.0

50

Note:
1. HACR type circuit breaker per NEC.

Electrical
Data

*

Indicates both downflow and horizontal units.

12½, 15, 20