Dimensions crossover piping – Trane VUV 750 CFM User Manual

Page 13

Advertising
background image

UV-SVN03D-EN

13

Dimensions

Crossover Piping

FLUSH

FLUSH

1 1/2"

1 1/4"

3"

24"

19 3/8"

3 5/8"
5 3/8"

RETURN

7/8" I.D. FIELD

CONN. W/ SHUT

OFF VALVE

7/8" I.D. FIELD

CONN. W/ SHUT

OFF VALVE

RETURN

TOP VIEW

SIDE VIEW

TOP VIEW

SIDE VIEW

16 5/8" DEPTH UNIT

21 1/4" DEPTH UNIT

SUPPLY

3"

24"

19 3/8"

3 1/2"
4 1/2"

8 1/4"
10"

SUPPLY

R

S

3 1/2"
4 1/2"

R

S

Notes: 1-3/8" o.d. and 2-1/8" o.d. crossover piping

1

Crossover piping is available for all 2 or 4-pipe coils selections. Trane pro-

vides the crossover for the cold water only. The crossover pipe is factory in-
sulated with 3/8"-thick insulation.

2

Expansion compensation between the factory piping package and the cross-

over piping is achieved using a flex hose rated at 250 psi working pressure.
flex hose is only available with factory mounted piping packages.

3

Expansion compensation for the crossover piping must be handled external

to the unit ventilator.

4

Crossover connections terminate in the same end pocket as the main coil con-

nection. The main coil connection for 2-pipe systems is the heating coil. the
main coil connection for 4-pipe systems is the cooling coil.