Trouble shooting checklist – Trane VUV 750 CFM User Manual

Page 32

Advertising
background image

32

UV-SVN03D-EN

Trouble Shooting

Checklist

Problem

Heating

Cooling

Cause

Correction

Room too cool

X

Room sensor is not properly set

Reset room sensor temperature

X

Clogged filter

Replace filter

X

Face and bypass damper, or coil valve is
malfunctioning.

Replace malfunctioning component, or
contact the control’s contractor, or if Trane
controls, see CNT-SVX04A-EN for more
information concerning Tracer™ controls.

X

OA damper is in the open position

Ensure OA damper is in the closed or
minimum outside air position.

X

Boiler pressure or temperature design
requirements not being met

On hot water and steam type units, check
the boiler pressure or temperature to
ensure that the requirements are being
met.

Room too cool
Unit utilizes Wall Fin auxiliary radiation:

X

Radiation controls malfunctioning

Check the operation of the wall fin
controls.

Room too hot

X

Room sensor is not properly set

Reset room sensor temperature

X

Clogged filter

Replace filter

X

Face and bypass damper, or coil valve is
malfunctioning.

Replace malfunctioning component, or
contact the control’s contractor, or if Trane
controls, see CNT-SVX04A-EN for more
information concerning Tracer™ controls.

X

OA damper is in the open position

Ensure OA damper is in the minimum
outside air position.

X

Chiller temperature design requirements not
being met

Check the temperature of the water
leaving the chiller to ensure that it meets
design requirements.

Motor

X

If the motor fails to start, and other motors on
the same circuit are functioning

Check the unit switch to ensure it is in the
ON position.

X

If the motor fails to start, and other motors on
the same circuit are functioning

Check for loose switch or motor
connection.