Installation – Trane VUV 750 CFM User Manual

Page 20

Advertising
background image

20

UV-SVN03D-EN

Modulating Water Valves (Option)
The actuator on the valve is a 24V, 3-
point floating valve. The actuator can
be easily removed from the valve body
by pressing in on the locking tab and
rotating the actuator 45° counter-
clockwise (See Figure 6a). The 2-way
valves are bi-directional flow. The 3-
way valves can be mixing or diverting
(See Figure 6b).

Note: The actuator must be removed if
soldering is being conducted near the
valve. High heat may cause damage to
the actuator’s plastic body/mecha-
nisms.

Figure 6a: Remove modulating valve
actuator by pressing in tab (inset) and
turning actuator 45° counterclockwise.

Figure 6b: Steam piping

On applications without the optional,
factory installed piping packages, it is
important to remove the cartridge as-
sembly from the valve body with the
provided tool (Figure 7).

Figure 7: Cartridge removal tool

Closed

Open

A

B

A

B

AB<->B

AB

B

AB<->A

A

AB

2-way valve

3-way valve

Use the following steps to complete
cartridge assembly removal:

1

Remove valve actuator.

2

Remove the cartridge assembly

from the valve body with the en-
closed tool.

3

Solder the valve in accordance with

normal soldering practices.

4

Re-install the cartridge after solder-

ing by tightening until it bottoms
out. The top surface of the car-
tridge will be flush with the top
edge of the body casting.

Note: Do not overtighten. Maxi-
mum torque is 40 in-lb.

5

Replace valve actuator and wire in

accordance with instructions.

Plumbing the Valve
The valve may be plumbed in any an-
gle but preferably not with the actua-
tor below horizontal level of the body.
Make sure there is enough room
around the actuator for servicing or re-
placement.

For use in diverting applications, the
valve is installed with the flow water
entering through the bottom AB port
and diverting through end ports A or
B. In mixing applications the valve is
installed with inlet to A or B and outlet
through AB.

Mount directly to the tube or pipe. Do
not grip the actuator while making or
tightening plumbing connections. Ei-
ther hold valve body by hand or attach
an adjustable spanner (38mm/1-1/2”)
across the hexagonal or flat faces on
the valve body. See Figure 8.

Figure 8: Proper plumbing technique
for modulating valves