General information – Trane VUV 750 CFM User Manual

Page 6

Advertising
background image

6

UV-SVN03D-EN

OA/RA Actuator (Option)
The OA/RA actuator provides true
spring return operation for positive
close-off of the OA/RA damper. The
spring return system of the actuator
closes the outside damper if power is
lost to the building. When ordered
with factory controls, the actuator is a
3-point floating design. A 2 to 10 VDC
actuator is available when other than
Trane controls are specified. See Table
1 for OA/RA technical data.

Note: Because the damper actuator is
a spring return type an inner spring
will close the damper upon loss of
power. If the need to service or replace
the actuator is required, the spring
must be "loaded" for the damper to
function properly. The term loaded
means that the blade must be held in
the return air position upon replace-
ment of the actuator.

Face and Bypass Actuator (Option)
The face and bypass damper actuator
incorporates a direct couple design. It
provides electronic protection against
overload. A limit switch is not includ-
ed, nor required as part of the design.
When reaching the damper end posi-
tion, the actuator automatically stops.
The gears can be manually disen-
gaged with a button on the housing.
See Table 2 for face and bypass actua-
tor specifications.

Modulating Water Valves (Option)
The modulating control valve provides
optimum control of hot and chilled wa-
ter flow in various heating and cooling
applications. They are designed to
provide sinusoidal valve actuator trav-
el and operate silently, resisting water
hammer.
The actuator on the valve is a 24V, 3-
point floating type. See Table 3 for
modulating water valve specifications.

Isolation Valve (Option)
The isolation valve is a two position
24V, spring return type valve. It pro-
vides added control in heating and
cooling applications when used in
conjunction with the face and bypass
damper.

Table 1: OA/RA actuator specification

Table 3: Mod. water valve specification

.

Power Supply

24 VAC

±

20% 50/60 HZ

24 VAC

±

10%

Power

Consumption

Running: 2.5 W

Holding: 1 W

Transformer
Sizing

5 VA (class 2-power source)

Overload

Protection

Electronic throughout 0 to

95-degree rotation

Control Signal 2 to 10 VDC

3-point floating with Trane controls

Angle of

Rotation

Maximum 95-degree
Adjustable with mechanical stop

Torque

35-inch/lb

Direction of
Rotation

Spring return reversible with CW/
CCW mounting

Position

Indication

Visual indicator, 0 to 95-degrees

Run Time

(nominal)

90-second constant (independent of
load)

Noise Level

Running: 30 dB

Power Supply

24 VAC

-

50/60 HZ

Power

Consumption

4 W

Max. Duty Cycle

15%

Nominal Timing

120 sec.

Operating Ambient
Temp.

0 to 65°C
32 to 150°F

Min./Max. Fluid Temp. 1 to 95°C

34 to 203°F

Operating Pressure

Differential

Max. - 4 bar (60 psi)

Pressure Rating

Static - 20 bar (300 psi)

Burst - 100 bar (1500 psi)

Flow Characteristic

Linear

Table 2: Face-bypass actuator specification

Table 4: Isolation valve specification

.

Power Supply

24 VAC

±

20% 50/60 HZ

24 VAC

±

10%

Power

Consumption

2 W

Transformer
Sizing

3 VA (class 2-power source)

Angle of

Rotation

Maximum 95-degree
Adjustable with mechanical stop

Torque

35-inch/lb

Direction of
Rotation

Reversible with switch L/R

Position

Indication

Clip-on indicator

Run Time

(nominal)

90-second constant

Manual

Override

External push button

Noise Level

Less than 35 dB

Control Signal

3-point floating

Power Supply

24 VAC

-

50/60 HZ

Power

Consumption

5 W

Max. Fluid Temp.

94°C
200°F

Min. Fluid Temp.

1°C
34°F

Max. Operating Pressure

300 psi

Max. Close-off Pressure

1/2" = 30 psi
3/4" = 20 psi
1" = 15 psi

General
Information

On heating coils, and two-pipe changeover applications, the valve is normally
open to help prevent the coil from freezing in-case of power loss.
For cooling, the valve is normally closed and opens when there is a call for cool-
ing. See Table 4 for isolation valve specifications.