5) condensation, 6) vent terminal (pipe and vent cap), Horizontal vent terminal clearances – Thomas & Betts RGM 405 User Manual

Page 11

Advertising
background image

Mfg No. 164771, Page 11

5) Condensation

Any length of single-wall vent pipe exposed to cold air or run
through an unheated area or an area with an ambient temperature
of 45°F or less must be insulated along its entire length with a
minimum of 1/2" foil-faced fiberglass, 1-1/2# density insulation.
Where extreme conditions are anticipated, install a means of con-
densate disposal.

6) Vent Terminal (Pipe and Vent Cap)

The vent system must be terminated with the type of vent cap
approved for use with this heater. The vent cap must be the same
size as the vent pipe. Use either a vent cap available from the

Roof or Building Overhang

3’ (1M) minimum

12”

(305mm)

minimum

6’ (2M)

minimum

Wall

Parapet or

Adjoining Building

Approved clearance

thimble for single-wall

vent pipe is required

when flue pipe extends

through combustible

materials.

Note position of vent

cap openings.

Pitch flue pipe down toward outlet

1/4” per foot for condensate drainage.

(NOTE: Applies to entire horizontal

vent run.)

Adjoining Building

Parapet or

Roof or Building Overhang

6’ (2M)

minimum

3’ (1M) minimum

12”

(305mm)

minimum

Wall

Approved clearance

thimble for single-wall

vent pipe is required

when flue pipe extends

through combustible

materials. Follow

the requirements

of the double-wall

pipe manufacturer.

Pitch flue pipe down toward

outlet 1/4” per foot for con-

densate drainage.

(NOTE: Applies to entire

horizontal vent run.)

Note position of

vent cap openings.

6” (152mm) minimum

Follow instructions on page 10 to join single

and double-wall pipe and to seal the connection.

Figure 8 - Horizontal Vent Terminals

Single-Wall Vent
Run and Single-
Wall Terminal

Single-Wall
Vent Run
and Double-
Wall
Terminal

Horizontal Vent Terminal Clearances

Structure

Minimum Clearances for Vent Termination

Location (all directions unless specified)

Forced air inlet within 10 ft (3.1m)

3 ft (0.9m) above

Combustion air inlet of another appliance

6 ft (1.8m)

Door, window, or gravity air inlet

4 ft (1.2m) horizontally

(any building opening)

4 ft (1.2m) below
1 ft (30cm) above

Electric meter, gas meter* and relief

4 ft (1.2m)

*Do not terminate the vent

equipment

horizontally

directly above a gas meter

Gas regulator*

3 ft (0.9m)

or service regulator.

Adjoining building or parapet

6 ft (1.8m)

Adjacent public walkways

7 ft (2.1m) above

Grade (ground level)

7 ft (2.1m) above

heater manufacturer (Option CC1) or a field-supplied cap. If the vent cap is
field-supplied, use a Type L Breidert Air-x-hauster

®

or equivalent vent cap.

(Type L Air-x-hauster

®

is a trademark of The G. C. Breidert Company.) Use

of a vent cap supplied by the pipe manufacturer is not permitted; the vent
cap must be the type approved for use with this heater. A different style
vent cap could cause nuisance problems or unsafe conditions.
See the illustrations in Figures 9A and 9B for requirements of vertical and
horizontal vent termination. The vent terminal pipe may be either single-
wall or double-wall (Type B). If double-wall pipe is used in the vent termi-
nal with a single-wall vent run, follow the instructions on page 10 to attach
the vent cap and to connect the double-wall pipe to the single-wall vent pipe
run.

A vent cap is required. Maintain a clearance
of 12" from the wall to the vent terminal cap
for stability under wind conditions.

Products of combustion can cause discolora-
tion of some building finishes and deteriora-
tion of masonry materials. Applying a clear
silicone sealant that is normally used to pro-
tect concrete driveways can protect masonry
materials. If discoloration is an esthetic prob-
lem, relocate the vent or install a vertical vent.

6’ (2M) minimum

6’ (2M) minimum

Approved clearance thimble

for single-wall vent pipe is

required when flue pipe

extends through

combustible materials.

Parapet or Adjoining Building

Vertical flue extension to

be 6” (152mm) higher than

anticipated snow depth but

no less than 2 feet (610mm)

above the roof.

Vertical pipe extension

must be insulated.

Roof Flashing

Roof - pitched

from 0 to 45°

Vertical flue extension

to be 6” (152mm) higher

than anticipated snow

depth but no less than

2 feet (610mm) above the

roof.

6” (152mm) minimum

Roof Flashing

Roof - pitched

from 0 to 45°

Approved clearance thimble

for single-wall vent pipe is

required when flue pipe extends

through combustible materials.

Follow the requirements of the

double-wall pipe manufacturer.

Follow instructions on page 10

to join single and double-wall

pipe and to seal the connection.

Parapet or Adjoining Building

Figure 9 - Vertical Vent Terminals

Single-Wall Vent
Run and Single-
Wall Terminal

Single-Wall Vent
Run and Double-
Wall Terminal

Advertising
This manual is related to the following products: