OPTIONAL ACCESSORIES (cont'd)
18. Optional Filter Cabinet (return air only)

A filter cabinet designed for 2" pleated disposable or permanent metal filters is shipped separately for field assembly and installation. Depending on
the option selected, filters are either shipped with the cabinet or are field-supplied.

To adapt to a variety of applications, the heater cabinet is designed so that the filter cabinet can attach on either the right side, the left side, or the rear
of the heater. The larger filter cabinets (left two tables below) are uniquely designed so that the same cabinet can be field-assembled and installed with
either a horizontal or vertical air inlet. The smaller filter cabinet in the table on the right is limited to Sizes 150 and 200 and is available with a
horizontal inlet only. All cabinets have door panels for easy filter removal for changing or cleaning.

All of the filter cabinets have a duct flange for attaching the inlet air duct. For inlet duct dimensions, see Paragraph 8.

Follow the step-by-step instructions included with the filter cabinet package to assemble and attach it to the heater.

Figure 21 - Filter Cabinets with Filter Arrangements and Filter Sizes

Sizes of Permanent or Pleated 2"

Filters for Options CW4, CW5, or CW6

S i z e

CFM

FPM

Filters

150

1800

281

(4) 16 x 16

2400

375

(4) 16 x 16

3000

469

(4) 16 x 16

200

2400

375

(4) 16 x 16

3000

469

(4) 16 x 16

250

3000

469

(4) 16 x 16

*4000

625

(4) 16 x 16

**5000

781

(4) 16 x 16

(4) 16 x 16

300

3000

469

(4) 16 x 16

*4000

625

(4) 16 x 16

**5000

781

(4) 16 x 16

(4) 16 x 16

350

4300

448

(6) 16 x 16

5000

521

(6) 16 x 16

*6000

625

(6) 16 x 16

400

4300

448

(6) 16 x 16

5000

521

(6) 16 x 16

*6000

625

(6) 16 x 16

NOTES:

* Requires 2" permanent filters.

** If using side inlets, two cabinets must be
installed, one on each side.

Sizes of Permanent or Pleated 2"

Filters for Options CW7, CW12, or

CW11

S i z e

CFM

FPM

Filters

150

1800

281

(4) 16 x 16

2400

375

(4) 16 x 16

3000

469

(4) 16 x 16

200

2400

375

(4) 16 x 16

3000

469

(4) 16 x 16

250

3000

313

(6) 16 x 16

4000

417

(6) 16 x 16

5000

521

(6) 16 x 16

300

3000

313

(6) 16 x 16

4000

417

(6) 16 x 16

5000

521

(6) 16 x 16

350

4300

448

(6) 16 x 16

5000

521

(6) 16 x 16

*6000

625

(6) 16 x 16

400

4300

448

(6) 16 x 16

5000

521

(6) 16 x 16

*6000

625

(6) 16 x 16

Option CW4 with 2" Pleated Filters

Option CW5 with 2" Permanent Filters

Option CW6 for Field-Supplied Filters

Attaches on Either Side of the Heater

Vertical (Top) or Horizontal Inlet Opening

"V" Filter Rack Arrangement

Filters for Options CW8, CW9, CW10

S i z e CFM FPM

2" Filters

Pleated Permanent

150 1800

375

(2) 12 x 32 (4) 12 x 16

2400

500

(2) 12 x 32 (4) 12 x 16

*3000 625

--

(4) 12 x 16

200 2400

500

(2) 12 x 32 (4) 12 x 16

*3000 625

--

(4) 12 x 16

Figure 21A -
Assembled with
Vertical Air
Inlet Opening

Figure 21B -
Assembled
with
Horizontal
Air Inlet
Opening

Figure 21C -
Small Filter
Cabinet for Sizes
150 and 200 only
-- Horizontal Air
Inlet Only

Option CW7 with 2" Pleated Filters

Option CW12 with 2" Permanent Filters

Option CW11 for Field-Supplied Filters

Attaches on the Rear of the Heater

Vertical (Top) or Horizontal Inlet
Opening

"V" Filter Rack Arrangement

Option CW8 with 2" Pleated Filters

Option CW9 with 2" Permanent

Filters

Option CW10 for Field-Supplied

Filters

Attaches on either Side or the Rear
of a Size 150 or 200 Heater

Horizontal Inlet Opening

"V" Filter Rack Arrangement

19. Mixing Cabinet (Outside and Return Air)

The optional mixing box for the Reznor

®

Model CAUA heater is designed

to provide the system with a supply air mixture of return air and outside
air. Any percentage of outside air can be supplied to the unit as long as the
air temperature entering the blower is 35°F or above. The mixing box is
available in an assortment of configurations with a selection of actuators
and controls. All mixing boxes are completely assembled at the factory for
field attachment to the rear of a Model CAUA heater.
Follow the instructions packed with the mixing box to cut out the opening
and attach the mixing box. If the mixing box has dampers, follow the

instructions for routing the damper motor wires, and connect the
wires according to the wiring diagram. If there are both return air and
outside air dampers, follow the directions to adjust the damper
linkage.

All mixing box inlet air openings have duct flanges for attachment of
ductwork. Ductwork must be attached to the outside air opening.
Removable door panels provide for filter access from either end of
the cabinet. If the box was ordered with optional filters, it is shipped
with the filters installed.