Venting and combustion air (cont'd), Vertical, Instructions and requirements for installing a – Thomas & Betts RGM 405 User Manual

Page 8: Installation instructions for option cc2

Advertising
background image

Form 405, Page 8

Figure 5D - Installation of a Typical Separated-
Combustion Unit with Horizontal Vent and Combustion
Air Pipes (Option CC6)

Building Overhang

3 ft (914mm)

minimum

6-15/16” (176mm)

Vent Pipe

- PITCH

TO

DRAIN

Adjoining

Building

3 ft (914mm)

minimum

Thimble

Wall

16”(406mm)

minimum

24”(610mm)

minimum

IMPORTANT NOTE: Exhaust cap must be installed so the baffles

are positioned on horizontal and vertical centerlines.

Building Projection

6ft (1829mm)

minimum

Concentric Adapter Box

Combustion Air Pipe

(PITCH TO DRAIN)

"Through-the-Wall" View of a typical

installation of a horizontal vent/inlet air

terminal and concentric adapter

(Option CC6)

7. Venting and Combustion Air (cont'd)

7A. Venting and Combustion Air Requirements for Separated-Combustion

Installation (must use either Option CC2 or CC6) (cont'd)

Instructions and Requirements for Installing a

Vertical

Vent Terminal/Combustion Air Inlet

(Requires Concentric Adapter Kit, Option CC2)

Vertical Vent Terminal/Combustion Air Package
(Option CC2) includes:

Field-supplied installation requirements:

Thimble (a thimble is not required if wall is of non-
combustible construction)

Flashing

Vent pipes (see requirements on pages 4 and 6)

Combustion air pipes (see requirements, pages 4 and 6)

Mounting brackets for concentric adapter box (or box
may be mounted flush, depending on building construc-
tion)

Taper-type reducers as required (see requirements on
page 6)

Qty Description

150,

250,300,

200

350,400

1

Complete Vertical Vent Kit

157156

54444

(Same as Option CC2)

1

Concentric Box Assembly

155392

68404

1

Exhaust

155631

53326

Terminal

1

Combustion

155635

53330

Air Inlet

1

Rubber seal for vent pipe

164492

164493

opening in concentric adapter

1

Tube of High Temperature

53335

53335

(450°F) Silicone Sealant

Side View

Screened

Exhaust

Cap

Inlet Air

Guard

Wall

Vent (Flue Exhaust) Pipe

Seal joints; see Require-

ment No. 5 on page 6.

Combustion Air Pipe

Seal Joints

Concentric Adapter

Maximum Length (See Requirement

No. 4 on page 6.)

Minimum length is 5 ft (1.5M)

60” (1524mm) maximum

12” (305mm) minimum

Top
View

Worksheet - Determine Length of
Vent Pipe through the Box

inches m m

Heater Side (max if +

6

152

diameter changes)
Width of Box

+

6

152

Bracket Length

+

__

___

Width of Roof

+

__

___

Inlet Pipe Height

+

__

___

Terminal Side (min) +

22

559

Length of Pipe

=

2. Prepare the concentric adapter box.
2a) Determine whether field-supplied brackets are required.
If used, attach

brackets securely; do not leave any unsealed holes in the adapter box.
If brackets are not used, when in-
stalled, the box should be tight against
the roof.

2b) Install the rubber seal and the

vent pipe. Locate the vent pipe open-
ing and place the rubber seal around
and over the edge of the metal.
Determine the length of the section of
vent pipe by adding the requirements.
On the heater side of all Sizes except
CAUA 250, the vent pipe must ex-
tend no more than 6" (152mm) (length
limit does not apply to Size 250 be-

Installation Instructions for Option CC2

1. Determine the location for the vent terminal on the roof, allowing room for the
concentric adapter box inside. A thimble may or may not be required depending
on building construction and/or local codes. Prepare a hole through the roof for
the combustion air pipe (Sizes 150 and 200, pipe is 6"; Sizes 250-400, pipe is 8").
The air inlet pipe must be flashed or sealed to the roof. Flashing is to be supplied
by the installer as required by roof construction and/or codes.

WARNING: All vent terminals must be positioned or
located away from fresh air intakes, doors and windows to
preclude combustion products from entering occupied
space. See Hazard Levels, Page 2.