Gas piping and pressures – Thomas & Betts RGM 405 User Manual

Page 13

Advertising
background image

Mfg No. 164771, Page 13

Sizing a Gas Supply Line

9. Gas Piping and Pressures

WARNING: This appliance is equipped for a
maximum gas supply pressure of 1/2 pound, 8
ounces, or 14 inches water column. Supply
pressure higher than 1/2 pound requires
installation of an additional lockup-type service
regulator external to the unit.

PRESSURE TESTING SUPPLY PIPING

Test Pressures Above 1/2 PSI: Disconnect the heater and manual
valve from the gas supply line which is to be tested. Cap or plug the
supply line.
Test Pressures Below 1/2 PSI: Before testing, close the manual
valve on the heater.

All piping must be in accordance with requirements outlined in the
National Fuel Gas Code ANSI Z223.1a (latest edition) or CAN/CGA-
B149.1 and B149.2 (See Paragraph 1). Gas supply piping installation
should conform with good practice and with local codes.
Unit heaters are orificed for operation with natural gas having a heating
value of 1000 (± 50) BTUH per cubic ft or propane gas with a heating
value of 2550 BTUH per cubic ft. If the gas at the installation site does
not meet these specifications, consult the factory for proper orificing.
Pipe joint compounds (pipe dope) shall be resistant to the action
of liquefied petroleum gas or any other chemical constituents of
the gas being supplied.
Install a ground joint union and manual shutoff valve upstream of the
unit control system as shown in Figure 13. The 1/8" plugged tapping in
the shutoff valve provides connection for a supply line pressure test
gauge. The National Fuel Gas Code requires the installation of a trap
with a minimum 3" drip leg. Local codes may require a minimum drip
leg longer than 3" (typically 6"). Bleed gas lines of trapped air.
Gas connection is either 1/2" or 3/4" depending on size and type of gas.

S i z e

Gas

Gas Connection

150-200

Natural

1/2"

250-400

Natural

3/4"

150-400

Propane

1/2"

Leak-test all connections by brushing on a leak-detecting solution.

WARNING: All components of a gas supply
system must be leak tested prior to placing
equipment in service. NEVER TEST FOR
LEAKS WITH AN OPEN FLAME. Failure to
comply could result in personal injury, property
damage or death.

Manifold or Orifice Pressure Settings

Measuring manifold gas pressure cannot be done until the heater is in
operation. It is included in the steps of the "Check-Test-Start" proce-
dure in Paragraph 22. The following warnings and instructions apply.

WARNING: Manifold gas pressure must never
exceed 3.5" w.c. for natural gas or 10" w.c. for
propane gas.

For Natural Gas: Manifold gas pressure is regulated by the combina-
tion valve to 3.5" w.c. Inlet pressure to the valve must be a minimum of
5" w.c. or as noted on the rating plate and a maximum of 14" w.c.

For Propane Gas: Manifold gas pressure is regulated by the combina-
tion valve to 10" w.c. Inlet pressure to the valve must be a minimum of
11" w.c. and a maximum of 14" w.c.
Before attempting to measure or adjust manifold gas pressure, the inlet

From Gas Supply

From

Gas

Supply

6” Drip Leg

NOTE:

Connections

shown are by

the installer.

To Controls

Manual

Gas Valve

Immediately upstream of the gas

supply connection, install a manual

shutoff valve with a 1/8” NPT

plugged tap accessible for test

gauge connection.

Ground Joint Union

Figure 13 -
Supply Piping
Connection

Capacity of Piping - Cubic Feet per Hour based on 0.3" w.c. Pressure Drop

Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)

Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)

Length

Diameter of Pipe

of 1/2"

3/4"

1"

1-1/4"

1-1/2"

2"

Pipe

Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane

20’

92

56

190

116

350

214

730

445

1100

671

2100

1281

30’

73

45

152

93

285

174

590

360

890

543

1650

1007

40’

63

38

130

79

245

149

500

305

760

464

1450

885

50’

56

34

115

70

215

131

440

268

670

409

1270

775

60’

50

31

105

64

195

119

400

244

610

372

1105

674

70’

46

28

96

59

180

110

370

226

560

342

1050

641

80’

43

26

90

55

170

104

350

214

530

323

990

604

90’

40

24

84

51

160

98

320

195

490

299

930

567

100’

38

23

79

48

150

92

305

186

460

281

870

531

125’

34

21

72

44

130

79

275

168

410

250

780

476

150’

31

19

64

39

120

73

250

153

380

232

710

433

175’

28

17

59

36

110

67

225

137

350

214

650

397

200’

26

16

55

34

100

61

210

128

320

195

610

372

Note: When sizing supply lines, consider possibilities of future expansion and increased requirements.

Refer to National Fuel Gas Code for additional information on line sizing.