9

4000

Installation

2.4.6

ATT Mark/Space Wiring

For an ATT using the Mark/Space field communications option, the following additional wiring connections must be

made. (Refer to Input Power Wiring in Section 6 to determine the minimum wire size required.). See Figure 2-6.

Run two twisted pairs of 18 AWG wire (Mark/Space wires) into the ATT through the conduit entry along with the

48 VDC power wiring.

Connect the Mark line to terminal 11, M/485-, and the Space line to terminal 12,

S/485+, on the terminal block assembly.

Figure 2-6: Typical Mark/Space Field Wiring

Details of RTU8130 with 8210 expansion
module and ATT termination board wiring

Varec

Model 4000

ATT

External
Power Supply

To Other

4-Wire

Transmitters

in Area 0

Ground shield at RTU8130 ONLY!

Do NOT ground shield at transmitter.

4 Conductor

Cable

18 AWG

Shielded

8203 With 8210

expansion module

Field Junction Box