Installation

Tank Gauge Transmitter

10

Installation and Operations Manual

2.5

Connecting the RTD

The following list shows how the ATT is wired to an RTD device. The ATT’s temperature circuit is designed to work

with a platinum or copper 3-wire RTD.

2.5.1

Connecting the Handheld Terminal

Figure 2-3 on page 6 shows how the 1200 Hand Held Terminal is connected to the ATTI bus on the ATT. The Model

268 can also be used to configure the ATT.

Warning!

The 1200 Hand Held Terminal on the ATT is not Intrinsically Safe. Care must be taken to only use in a non-hazardous
environment

Wire as follows:

Connect the RTD's A terminal to the ATT's terminal 6, A.

Connect the RTD's B terminal to the ATT's terminal 5, C.

Connect the RTD's C terminal to the ATT's terminal 4, C.

2.5.2

Wiring Completion

Caution!

Do not overtighten metal plugs used to seal wiring compartment ports. Overtightening may damage the housing.

Properly seal the 1/2-inch NPT conduit entry. Install cover and tighten to ensure that the O-ring seal is adequately

compressed. Proper sealing of all ports is necessary to prevent moisture or other contamination from entering the

wiring compartment.

2.5.3

Installation Checkout

After a thorough check that all connections are correctly made and that all covers and plugs are installed, turn on

power to the ATT. Proceed to Chapter 3, Configuration.

2.5.4

Installation Checklist

The steps required in the installation process are summarized in the following checklist. Since each step is detailed

specifically with accompanying notes, cautions, and warnings, be sure to refer to the sub-sections indicated for further

information.

Step

Sub-Section(s) Reference

Unpack the ATT and check the packing list.

Unpacking

Verify that the required input power is available.

Mounting the ATT, Wiring

Mount the ATT.

Mounting the Equipment

Ground the ATT.

Grounding the Equipment

Route the conduit between the ATT and other

devices and seal all ports.

Wiring Completion

Wire the host communications.

Connecting Host Communication

Wire the RTD

Connecting the RTD

Wire the input power connections.

Connecting Input Power

Apply power to the ATT.

Installation Checkout

Wire the Model 1200 Handheld Terminal

Connecting Handheld Terminal

Proceed to ATT configuration procedure.

ATT Configuration (Section 3)