Weil-McLain 88 Water and steam boilers — Series 2 —

for Gas, Light Oil, & Gas/Light Oil-Fired Burners

18

Part No. 550-100-068/1009

Connect steam boiler piping

(continued)

Drawing legend & notes

(Figure 23 through Figure 26)

Riser pipes (one for each supply intermediate section)



Horizontal pipes needed to offset the header to allow for expansion and contraction of the header



Steam supply must be located between last riser connection and equalizer elbow



Equalizer elbow — full size or reducing



Equalizer pipe



Close nipple at Hartford loop tee to reduce water hammer potential



Condensate return line (gravity or pumped)



Minimum 4 inches between water line and top of Hartford loop return nipple



Boiler water line — all automatic water level controls must be set to maintain this level



Minimum 24 inches between water line and bottom of header