Weil-McLain 88 Water and steam boilers — Series 2 —

for Gas, Light Oil, & Gas/Light Oil-Fired Burners

4

Part No. 550-100-068/1009

Installation must comply with —

State, provincial and local plumbing, heating and electrical

1.

codes.
Regulations of servicing utilities.

2.

ASME Section IV, Low Pressure Boiler and Pressure Vessel Code.

3.

National Fuel Gas Code, ANSI/NFPA 54, when applicable.

4.

National codes where applicable.

5.

Before selecting boiler location

Check for nearby connections to:

1.

Fuel supply.

a.

Electrical power.

b.

System water or steam piping.

c.

Venting systems - see

d. page

29.

Combustion and ventilation air supply — see

e. page

5.

Check area around boiler. Remove any combustible materials,

2.

gasoline and other flammable vapors and liquids.

Failure to keep boiler area clear and free of combustible

materials, gasoline and other flammable liquids and
vapors can result in severe personal injury, death and
substantial property damage.

Provide clearance around boiler

Provide minimum clearances to combustible materials:

1.

"OILER

s

— 24 inches.

"OILER

s

— 48 inches.

"OILER

s

— 9 inches.

"OILER

s

— 9 inches.

"OILER

s

— 6 inches.

3INGLE WALL

s

– 18 inches.

$OUBLE WALL

s

– refer to vent pipe manufacturer's

recommendations for vent pipe clearances.

Boiler may be installed on combustible flooring.

2.

See

3.

page 36 for boiler dimensions.

Flue pipe/breeching clearances take precedence over

jacket clearances.

Provide minimum clearances for servicing:

4.

,EFT

s

— for cleaning and tankless heater removal –

39 inches.

2EAR

s

— for breeching — 36 inches.

Allow sufficient space on remaining sides for cleaning, servicing

s

and burner installation. See burner literature for length and
recommended service clearances.

Lay a foundation, if needed

Floor construction and condition must be suitable for weight of

1.

boiler when filled with water. See page 35 for approximate boiler
operating weight.
A level concrete or brick foundation, constructed per

2. Figure

1

and

Figure 2 is required when:

A floor could possibly become flooded.

a.

Non-level conditions exist.

b.

Before installing boiler

Boiler foundation, when required

&IGURE

Boiler foundation (see

&IGURE

Figure 1)

"OILER

NUMBER

,ENGTH

L

(inches)

488

33

588

41

688

49

788

57

888

65

988

73

1088

81

1188

89

1288

97

1388

105

1488

113

1588

121

1688

129

1788

137

1888

145