Ratings

Boiler

model

number

I=B=R

burner

capacity

Gross
I=B=R

output

Net I=B=R ratings

Boiler

H.P.

Combustion

efficiency

Thermal

efficiency

Net

firebox

volume

Flue

gas

volume

Positive

pressure

in firebox

Flue

outlet

diameter

Boiler

water

content

Packaged

boiler

weight

Light oil

GPH

Gas

MBH

MBH

Steam

Sq. Ft

Steam

MBH

Water

MBH

Oil

Gas

Oil

Gas

Cubic

feet

CFM

Inches

W.C.

Inches Gallons

Pounds

Notes:

1, 10

2, 3

2, 4

5, 6

8

8

8

7

9

488R

6.9

996

827

2,583

620

719

24.7

87.5

84.8

85.6

83.1

11.02

376

0.60

10

109

2860

488

7.0

1,010

839

2,621

629

730

25.1

87.5

84.8

85.6

83.1

11.02

370

0.60

10

109

2860

588

9.4

1,356

1,126

3,521

845

979

33.6

87.0

84.4

85.6

83.1

14.45

507

0.63

10

132

3340

688

11.8

1,701

1,413

4,469

1,072

1,229

42.2

86.7

84.1

85.6

83.1

18.08

639

0.65

10

155

3820

788

14.2

2,046

1,700

5,463

1,311

1,478

50.8

86.5

83.9

85.6

83.1

21.61

772

0.67

12

178

4345

888

16.6

2,382

1,987

6,427

1,543

1,728

59.4

86.3

83.7

85.6

83.1

25.14

906

0.69

12

201

4925

988R

17.2

2,482

2,062

6,671

1,601

1,793

61.6

86.2

83.7

85.6

83.1

28.67

1,031

0.70

14

224

5600

988

18.8

2,737

2,274

7,358

1,766

1,977

67.9

86.2

83.7

85.6

83.1

28.67

954

0.70

14

224

5600

1088R

20.0

2,887

2,399

7,763

1,863

2,086

71.7

86.2

83.6

85.6

83.1

32.20

1,184

0.71

14

247

6130

1088

21.5

3,082

2,561

8,283

1,988

2,227

76.5

86.2

83.6

85.6

83.1

32.20

1,101

0.71

14

247

6130

1188

23.5

3,428

2,848

9,213

2,211

2,477

85.1

86.1

83.5

85.7

83.1

35.76

1,299

0.72

14

270

6695

1288

26.0

3,773

3,135

10,147

2,434

2,726

93.7

86.0

83.5

85.7

83.1

39.26

1,443

0.73

14

293

7260

1388

28.5

4,119

3,422

11,071

2,657

2,976

102.2

86.0

84.4

85.7

83.1

42.79

1,588

0.74

14

316

7890

1488

31.0

4,464

3,709

12,000

2,880

3,225

110.8

86.0

83.4

85.7

83.1

46.32

1,735

0.75

16

339

8410

1588

33.0

4,809

3,996

12,925

3,102

3,475

119.4

85.9

83.3

85.7

83.1

49.85

1,854

0.76

16

362

9005

1688R

34.5

4,979

4,137

13,383

3,212

3,597

123.6

85.9

83.3

85.7

83.1

53.38

2,003

0.77

16

385

9525

1688

35.5

5,155

4,283

13,854

3,325

3,724

127.9

85.9

83.3

85.7

83.1

53.38

1,945

0.78

16

385

9525

1788

38.0

5,494

4,570

14,783

3,548

3,974

136.5

85.9

83.3

85.7

83.1

56.91

2,152

0.79

18 *

408

9780

1888

40.5

5,845

4,857

15,713

3,771

4,123

145.1

85.9

83.3

85.7

83.1

60.44

2,303

0.80

18 *

431

10775

See below to specify complete model number.

1.

Burner input based on maximum of 2,000 feet altitude. For other

2.

altitudes, consult Weil-McLain distributor/agent or sales office.

No. 2 fuel oil — Commercial Standard Spec CS75-56. Heating

3.

value of oil = 140,000 Btu per gallon.

Gas pressure required at burner gas train inlet for rated burner

4.

input; based on 1,000 Btu per cubic foot natural gas, specific
gravity of 0.60. Refer to burner manual for required pressure.

Gross I=B=R ratings have been determined under the I=B=R provision

5.

governing forced draft boiler-burner units.

Flue gas volume at outlet temperature.

6.

Net I=B=R ratings are based on net installed radiation of sufficient

7.

quantity for the requirements of the building.
Nothing need be added for normal piping and pick-up.
Water ratings are based on a piping and pick-up allowance of 1.15.
Steam ratings are based on the following allowances: 488 – 588 =
1.333; 688 = 1.323; 788 = 1.301; 888 = 1.289; 988 – 1888 = 1.288.
An additional allowance should be made for gravity hot water systems
or for unusual piping and pick-up loads.
Consult local Weil-McLain distributor/agent or sales office.

With 0.10" W.C. positive pressure at flue collar.

8.

Water boilers tested for 80 PSIG, ASME water working pressure.

9.

Steam boilers tested for 15 PSIG, ASME steam working pressure.

*

Flue collar connection is oval, 16

56 " x 19(6 "