Inverter Specifications

975-0337-01-01

A–3

Inverter Specifications

All inverter specifications are at nominal conditions; 1000 W resistive
load, 12 Vdc inverting on the IP1012 AL, 120 Vac, unless otherwise
specified.

Inverter specifications

Output wave form

Modified sine wave

Output power continuous

1000 Vac continuous

Surge rating

3000 VA for 30 seconds at –40 °F to 77 °F
(–40 °C to 25 °C)
See Figure A-1 for output at different
temperatures.

Operating voltage range

10.4 Vdc to 16.0 Vdc

Input DC voltage rating

12 Vdc

Output voltage

120 Vac RMS

Output voltage regulation

108 to 125 Vac under steady state 0 to 1000 W
load with 10.6 to 14.5 Vdc input at 25 °C
(77 °F)

108 to 132 Vac up to 1000 W, 10.6 to 16 Vdc
input at – 40 °F to 185 °F (–40 °C to 85 °C)

Output frequency

60.0 ± 0.1 Hz from – 40 °F to 185 °F (– 40 °C to
85 °C) ambient temperature

Power factor allowed

All (0 to 1, leading or lagging)

Peak efficiency

Greater than 93% at 12.6 Vdc input at 77 °F
(25 °C)

Idle power consumption

Less than 15 W (inverting with 120 Vac output
and no load)

Auto-shutdown mode

Inverter output is less than 15 ±5 W and battery
is less than 13 Vdc for 8 hours

Off mode power
consumption

Less than 120 mW when inverter switch is off or
in auto off mode