3 adjustment without medium – VEGA VEGAMET 513 User Manual

Page 21

Advertising
background image

VEGAMET 513

21

Settings in the "reduced menu"

Adjustment example

You know the data of the sensor, i.e. you
know that at 0 % filling the sensor delivers a
current of 4.2 mA and at 100 % filling a cur-
rent of 15.5 mA. Enter these values in the
menu items.

6.3 Adjustment without medium

Adjustment without medium means that you
carry out the adjustment independent of the
actual level. For this adjustment procedure
you have to enter two sensor current values
(4 … 20 mA) corresponding to the levels
0 % and 100 %.

Enter in these two menu items the values of
the senor. Use the [+] and [–] keys to set the
values and [OK] to save the values.

0%
at
mA

4,200

100%
at
mA

15,500

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Adjust
ment

with
medium

without
medium

0%
at

mA

4,000

100%
at
mA

20,000

Meas. value
indication

4.2 mA at 0 %

15.5 mA at 100 %

Advertising