7 Settings in the "extended menu"

7.1 Configuration of measurement loop

Settings in the "extended menu"

The measurement loop configuration is nor-
mally already done at the factory. Should a
fundamental modification of the measurement
loop configuration be necessary, a "Reset to
single measurement" must first be carried out
(in the menu "Additional functions", "Reset
VEGAMET"). Only then can you modify the
adjustments in the menu items Application,
Sensor type, Mode and Option. You should,
therefore, work on the individual menu items
in the given sequence. The selection or ad-
justment possibilities always depend on the
adjustment in the previous menu item. If, for
example, in the menu item Application "Level"
is adjusted, only the sensor mode that is
suitable for level detection can be selected in
the menu item "Sensor type".
As soon as you have carried out and con-
firmed an adjustment in the menu item "Op-
tion", the following message appears on the
display "TAG being created!".

You choose the application 4/20 mA when
you want to connect a sensor of another
manufacturer to the VEGAMET.

In the following illustrations, further applica-
tion modes are shown. In addition, you will
see there which adjustments you have to
carry out in the menu items "Sensor type" and
"Mode".

Confi-
gura-
tion

Config
in-
puts

Config
meas.
loop

TAG 1
level

Appli-
cation

level

Sensor
type

Hydro-
static

Mode

Stan-
dard

Option

no
option

Sensor
coordi-
nation

TAG-
name

TAG -
No. 1

Posi-
tion A

In-
put 1

Param.
TAG-
No. 1

TAG -
No. 1
%

xx,x

0/4-20mA
Gauge
Pressure

capacitive
VEGADIF
VEGABAR