Special function: Manual correction

Manual offset correction

(only with hydrostatic pressure transmitters)
This correction can be carried out to com-
pensate changes of the sensor values due
to ageing. In oder to do this, the sensor must
be in an unpressurized condition (empty
vessel).

Param.
TAG-
No.
1

TAG -
No. 1
%
xx,x

Adjust-
ment

Signal
condi-
tioning

Out-
puts

Simu-
lation

Special
functions

Reset
Level

Manual
corr.

Offset
cor-
rec-
tion

Offset
correc-
tion
OK?

Cor-
rection
now !
OK ?

Cor-
rection
now !
OK ?

Real
value
corr.

Real
value
corr.
OK?

Correc-
tion
%

0,0

Manual real value correction

In the menu item "Correction % 0.0" you can
enter a percentage value which corresponds
to the actual level.