VEGAMET 513

23

Settings in the "reduced menu"

6.5 Integration time

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Adjust
ment

Signal-
condit
ioning

Sca-
ling

Integr
ation
time s

0

Meas. value
indication

If the integration time is set to 0 s (factory
setting), each quick change of the product
surface (e.g. waves) will be immediately
detected and interpreted as level change. All
output values of VEGAMET will react
immediately to the wave movements. To
avoid this, the integration time can be
increased (max. 600 s are possible with
VEGAMET). The higher the time adjustment,
the slower the measurement reacts.

6.6 Outputs

Meas. value
indication

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Adjust
ment

Signal-
condit
ioning

Out-
puts

Current
out-
put 1

4/20mA

Volt
out-
put 1

0/10V

0/20mA
20/4mA
20/0mA

10/2V
10/0V
2/10V

The current output of VEGAMET is adjusted
to 4 … 20 mA. By pushing [+] or [–] and
[OK] the outputs can be adjusted to the
following values: 0/20 mA, 20/4 mA and
20/0 mA.

For voltage output, the following options are
available apart from the preadjustment
(0/10 V): 10/2 V, 10/0 V and 2/10 V.

6.7 Simulation

To check outputs and connected instru-
ments, you can adjust any individual
percentage value with the keys [+] and [–] in
this menu item. Initial point is always the
actual measured value. The indicated value
flashes when simulation is activated. 15
minutes after setting the simulated value, the
simulation automatically terminates and
resets to meas. value indication.

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Ad-
just
ment

Signal-
condit-
ioning

Out-
puts

Simu-
lation
Now !
OK ?

Simu-
lation

Simu-
lation
%

xx,x

Meas. value
indication