VEGA VEGABAR 65 Profibus PA User Manual

Page 47

Advertising
background image

?

When an additional instrument is connected, the segment fails.

l

Max. supply current of the segment coupler exceeded

à Measure the current consumption, reduce size of segment

?

Wrong presentation of the measured value in Simatic S5

l

Simatic S5 cannot interpret the number format IEEE of the
measured value

à Insert converting component from Siemens

?

In Simatic S7 the measured value is always presented as 0

l

Only four bytes are consistently loaded in the PLC

à Use function component SFC 14 to load 5 bytes consistently

?

Measured value on the indicating and adjustment module does not
correspond to the value in the PLC

l

The menu item "Display - Display value" is not set to "PA-Out"

à Check values and correct, if necessary

?

No connection between PLC and PA network

l

Incorrect adjustment of the bus parameter and the segment
coupler-dependent baud rate

à Check data and correct, if necessary

?

Instrument does not appear during connection setup

l

Profibus DP cable pole-reversed

à Check cable and correct, if necessary

l

Incorrect termination

à Check termination at the beginning and end points of the bus

and terminate, if necessary, according to the specification

l

Instrument not connected to the segment, double assignment
of an address

à Check and correct, if necessary

In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.

?

E

013

l

no measured value available

9)

à Exchange instrument or return instrument for repair

?

E

017

l

Adjustment span too small

à repeat with modified values

9)

Fault message can also appear if the pressure is higher than the nominal
range.

Checking Profibus PA

Fault messages via the
indicating/adjustment
module

VEGABAR

65 • Profibus PA

47

8 Maintenance and fault rectification

28253

-

EN

-090522

Advertising