VEGA VEGABAR 65 Profibus PA User Manual

Page 54

Advertising
background image

Dynamic behaviour output

Run-up time approx.

10 s

90 %

100 %

10 %

t

t

T

A

t

t

S

2

1

Fig. 28: Sudden change of the process variable, dead time t

T

, rise time t

A

and step response time t

S

1

Process variable

2

Output signal

Dead time

150 ms

Rise time

100 ms (10 … 90 %)

Step response time

250 ms (ti: 0 s, 10 … 90 %)

Damping (63 % of the input variable)

0 … 999 s, adjustable

Input variable

Adjustment

Adjustment range of the min./max. adjustment relating to the nominal measuring range:

-

percentage value

-10 … 110 %

-

pressure value

-20 … 120 %

Adjustment range of the zero/span adjustment relating to the nominal measuring range:

-

zero

-20 … +95 %

-

Span

-120 … +120 %

10)

-

Difference between zero and span

max. 120 % of the nominal range

Recommended max. turn down

10 : 1 (no limitation)

Nominal measuring ranges and overload capability in bar/kPa

Nominal range

Overload, max. pressure Overload, min. pressure

Gauge pressure

0 … 0.1 bar/0 … 10 kPa

15 bar/1500 kPa

-1 bar/-100 kPa

10)

Values less than -1 bar cannot be set.

54

VEGABAR

65 • Profibus PA

10 Supplement