VEGA VEGABAR 65 Profibus PA User Manual
Page 54
Dynamic behaviour output
Run-up time approx.
10 s
90 %
100 %
10 %
t
t
T
A
t
t
S
2
1
Fig. 28: Sudden change of the process variable, dead time t
T
, rise time t
A
and step response time t
S
1
Process variable
2
Output signal
Dead time
≤
150 ms
Rise time
≤
100 ms (10 … 90 %)
Step response time
≤
250 ms (ti: 0 s, 10 … 90 %)
Damping (63 % of the input variable)
0 … 999 s, adjustable
Input variable
Adjustment
Adjustment range of the min./max. adjustment relating to the nominal measuring range:
-
percentage value
-10 … 110 %
-
pressure value
-20 … 120 %
Adjustment range of the zero/span adjustment relating to the nominal measuring range:
-
zero
-20 … +95 %
-
Span
-120 … +120 %
10)
-
Difference between zero and span
max. 120 % of the nominal range
Recommended max. turn down
10 : 1 (no limitation)
Nominal measuring ranges and overload capability in bar/kPa
Nominal range
Overload, max. pressure Overload, min. pressure
Gauge pressure
0 … 0.1 bar/0 … 10 kPa
15 bar/1500 kPa
-1 bar/-100 kPa
10)
Values less than -1 bar cannot be set.