Ex-version, Fig. 2.9 mounting – VEGA VEGASWING 83 fail safe and signal conditioning instrument VEGATOR 526 Ex User Manual

Page 17

Advertising
background image

VEGASWING 81 W5 Ex.C, 83 W5 Ex.C fail safe

17

Fig. 2.9

Mounting

Ex-version

Ex-separating chamber

To ensure sufficient “Air and creeping
distances“, an Ex-separating chamber must
be mounted to the connections of VEGATOR.
Loop the lines through the Ex-separating
chamber and connect the lines. Fasten the
Ex-separating chamber with the lower holding
screw. Note the operating instruction of the
carrier BGT 596␣ Ex.

Blind cover

Mounting in carriers

When you mount your VEGATOR with Ex-
approval in a carrier, you have to use a VEGA-
Ex-module. Keep a distance of at least 10 mm
(2 TE) to modules of other manufacturers.
When you want to mount VEGATOR to the
complete left in the carrier, you have to mount
a blind cover of at least 20 mm (4 TE) in front
of the module of the instrument.

Protection with Ex-applications

In Ex-applications a protection of IP 20 must
be kept in mounted condition. Hence cover
the gaps or free modules from the front by
appropriate blind covers.

Fig. 2.10

Ex-separating
chamber

Module with multipoint
connector acc. to DIN
41␣ 612 for carrier
(back view)

2

4

6

8

12

20

28

24

22

10

14

16

18

30

32

d b z

26