Failure

Reason / Removal

Before pushing the set-up key (3) Check the following failure reasons:

- line break
- interpolation of the sensor lines
- short-circuit
- undefined position of the hook switch (6) or the

slide switch (7)

- electronics defect on VEGASWING or on VEGATOR

In case of an electronics defect, call our service department.

After set-up

- set-up key was not pushed long enough

Repeat the set-up (push set-up key (3) for 4␣ …␣ 6␣ s)

Diagnosis

5 Diagnosis

5.1 Failure removal

Via the condition of the LED in the front plate
of VEGATOR two failures can be detected:
- failure during set-up
- failure detection within the self-monitoring.

In both cases the level and fail safe relays de-
energize.

VEGATOR 526 Ex

on

lights

lights

In case of set-up failures, a new start must be
made (switch off voltage supply and switch on
again) and repeat the set-up.

When failures are detected, first of all switch
off the voltage supply, then remove the failure
(e.g. line break) and switch on the voltage
supply again. It is not necessary to repeat the
set-up.

lights

off

VEGATOR 526 Ex

on

lights

off

lights