Set-up – VEGA VEGASWING 83 fail safe and signal conditioning instrument VEGATOR 526 Ex User Manual

Page 25

Advertising
background image

VEGASWING 81 W5 Ex.C, 83 W5 Ex.C fail safe

25

Ready condition before set-up

Pre-requirements to carry out the set-up
- VEGASWING is mounted in its final position

and the tuning fork is not covered with the
medium

- the failure-LED is dark

• Push the lowered set-up key (3) for approx.

4␣ …␣ 6␣ seconds.

With the set-up an adaption of VEGATOR to
VEGASWING is made. The actual resonance
frequency is detected by VEGATOR as
current and saved as reference value.

Condition up to approx. 10 secs. after
set-up

Set-up

VEGATOR 526 Ex

on

VEGATOR 526 Ex

on

Yellow LED lights

Green LED in set-up key lights

Green LED lights

Green LED lights

Yellow

- relay control lamp (2)
- the yellow control lamp reacts acc. to the

adjusted mode (A/B).

- generally the relay control lamp shows the

safe (currentless) condition of the relays.

- a dark control lamp means that the relay is

in activated (current) condition.

Set-up

After connecting VEGASWING 8…␣ W5␣ Ex and
inserting VEGATOR 526␣ Ex in the carrier or the
single housing, the meas. system is ready for
operation.

• Screw the signal conditioning instrument.

With the lowered set-up key (3) you can set-
up the level detection.

VEGATOR 526 W Ex

on

Yellow LED lights
(= level relay de-energized)

Green LED in set-up key
flashes (= set-up not yet
carried out)

Green LED lights
(= supply voltage on)

Condition approx. 10 secs. after set-up

Advertising