Connection examples for overvoltage arresters, Electrical connection, Vessel without cathodic corrosion protection – VEGA VEGASWING 83 fail safe and signal conditioning instrument VEGATOR 526 Ex User Manual

Page 20: Cu-line

Advertising
background image

20

VEGASWING 81 W5 Ex.C, 83 W5 Ex.C fail safe

Electrical connection

E2

E1

A2

A1

A1

A2

E2

E1

1
2

Typ

B62-27

Typ

B62-27G

d30

d32

E86 Ex

Connection examples for overvoltage arresters

Vessel without cathodic corrosion protection

t

o potential

equalisation
line

min. 4 mm

2

Cu

External
earth terminal

optionally
overvoltage arrester

Note :

- Use suitable cable, optionally with metal cover or screen. Cable with metal cover or screen

(as shown) do not require a potential equalization along the complete intrinsically safe circuit.
Just connect the screen or metal cover to the overvoltage arrester (test voltage

␣ 500␣ V).

- The capacity of the screen must correspond at least to that of a 1,5 mm

2

Cu-line.

Earth / PA
connection terminal

Outer
isolation

Outer
isolation

Screen

Screen

Metal housing isolated
mounted or plastic
housing

Overvoltage arrester
type B62 - 27 Ex 0
or B62 - 27 Ex

Overvoltage
arrester

Line length

␣ 50 m

VEGASWING

VEGATOR
526 Ex

Ex-area

Not Ex-area
(control room)

Advertising