VEGA VEGASWING 83 fail safe and signal conditioning instrument VEGATOR 526 Ex User Manual

Page 9

Advertising
background image

VEGASWING 81 W5 Ex.C, 83 W5 Ex.C fail safe

9

Signal conditioning instrument VEGATOR 526 Ex

General

Series

module unit for carrier BGT 596 Ex

Dimensions

W = 50,8 mm (10 TE), H = 128,4 mm, D = 162 mm

Weight

approx. 440 g

Ambient conditions

Ambient temperature

-20

°

C … +60

°

C

Storage and transport temperature

-40

°

C … +70

°

C

Power supply

Operating voltage

U

N

= 24 V AC (20 … 28 V AC); 50/60 Hz

U

N

= 24 V DC (16 … 60 V DC

Power consumption

approx. 11 VA or 8 W

Electrical connection

multipoint connector DIN 41 612,
series F (d, z) 32-pole

Electrical protective measures

Protection class

II (in housing type 589-10 Ex)

Overvoltage category

II

Protection
- mounted in housing type 589…

IP 30

Protection
(mounted into carrier
BGT 596 Ex with Ex-module)
- front side (completely equipped)

IP 30

- upper and lower side

IP 20

- wiring side

IP 00

Inputs

Number

1

Data transmission

analogue, 4 … 20 mA

Current limitation

24 mA (permanently shortcircuit proof)

Sensor supply voltage

approx. 15 … 18 V DC

Connection line

2-wire (screened)

Resistance per conductor

max. 35

Function

Integration time
- switch on delay

0,5 s

- switch off delay

1,0 s

Product description

Advertising