VEGA VEGAFLEX 52P (Profibus PA) User Manual

Page 26

Advertising
background image

26

VEGAFLEX 51P and 52P

Electrical connection

In the so-called Fieldbus Intrinsically Safe
Concept (FISCO), the general conditions for
an Ex safe bus configuration have been laid
down. Therein the participants and the bus
cables with their electrical data have been
determined, so that the linking of these com-
ponents always meets the Ex requirements.
A more time-consuming Ex calculation is
therefore not necessary. You can build your
Ex bus according to the IEC standard 1158-
2.

The Ex segment coupler delivers a controlled
power supply to the PA bus. All other compo-
nents (field instruments and bus terminators)
are only consumers. A field instrument must
consume at least 10 mA. Ideally, an individual
sensor should not consume more than
10 mA, so that the number of instruments can
be as large as possible.

VEGA PA sensors, whether Ex or non Ex,
consume a constant current of 10 mA. Ac-
cording to the Profibus specification, this is
the minimum participant current. With VEGA
sensors it is therefore possible to connect 10
sensors (also in Ex environment) even with a
limited energy supply from the Ex segment
couplers.

Watch out for potential losses

Due to potential losses, earthing on both
sides without a potential equalisation system
is not allowed in Ex applications. If an instru-
ment is used in hazardous areas, the re-
quired regulations, conformity and type
approval certificates for systems in Ex areas
must be noted (e.g. DIN 0165). Please also
note the approval documents with the safety
data sheet attached to the Ex sensors.

Ex protection

If an instrument is used in hazardous areas,
the required regulations as well as the dust-
Ex certificates of VEGAFLEX for systems in
dust-Ex areas must be noted.

Electrical data of the cables

R

DC

No. of A in

Z

31.25kHz

C in

Damping

Screen

cores

mm

2

nF/km

SINEC 6XV1

44

W/km

2

0.75

100

W

< 90

< 3 dB/km

Cu braiding

830-5AH10

+/- 20

W

39 kHz

(Siemens)

SINEC L26XV1 44

W/km

2

0.75

100

W

< 90

< 3 dB/km

Cu braiding

830-35H10

+/- 20

W

39 kHz

(Siemens)

3079A

105

W/km 2

0.32

150

W

29.5

< 3 dB/km

Foil

(Belden)

39 kHz

Advertising