48

VEGAFLEX 51P and 52P

5.3 Error rectification

Error

Error rectification

E 013

Sensor cannot find

- Message is displayed during the warm-up

level echo

phase.

- If the message remains, the DK-value

of the medium could be too low.

Check the useful level and noise level.
See 4.2 Adjustment with adjustment module
MINICOM / Useful and noise level (6).
If the message still remains, carry out a
new adjustment.

E 017

Adjustment span too small

Carry out a new adjustment.
Make sure that the difference between min.
and max. adjustment is at least 10 mm.

E 036

Software update incorrect

Return the instrument for repair.

- Sensor requires programming (service).
- Failure message remains also during a

current programming.

E 040

Hardware failure /

Check all connection cables.

electronics defect

Contact our service department.

Diagnostics