Vessel without cathodic corrosion protection, Electrical connection – VEGA Capacitive electrodes EK … with signal conditioning instrument User Manual

Page 25

Advertising
background image

Capacitive electrodes EK with signal conditioning instrument

25

Capacitive electrode with external overvoltage protection unit

Vessel without cathodic corrosion protection

E2

E1

A2

A1

A1

A2

E2

E1

1

2

Typ

B62-36G

Typ

B62-36G

B

A

Ex-area

Not-Ex-area
(control room)

optionally overvoltage arrester

optionally overvoltage arrester
B62 - 36 G Ex 0 (metal housing) or
B62 - 36 G Ex (plastic housing)
(L

i

= 0,15 mH, C

i

= 1,5 nF)

Electrode EK

Outer
isolation

Outer
isolation

Screen

Screen

Signal conditioning
instrument or safety
barrier

Earth/ PA-connection
terminal

to potential euqaliza-
tion line

External earth terminal

Note:

[A] Between control room and overvoltage protection system a suitable cable, if necessary a metal cover or

screen, should be used. Screen or metal cover - if necessary - must only be connected to the electrode
side of the overvoltage arrester.

[B] Between overvoltage protection system and capacitive electrode a suitable cable with metal cover, screen

or a suitable cable with metal protection tube should be used (screen, metal cover or protection tube must
be connected to the potential equalisation).

Test voltage of the cable A and B:

£ 500 V AC

min. 4 mm

2

Cu

Vessel
Zone 0

Electrical connection