Vessel with/without cathodic corrosion protection – VEGA Capacitive electrodes EK … with signal conditioning instrument User Manual

Page 26

Advertising
background image

26

Capacitive electrodes EK with signal conditioning instrument

A1

A2

E2

E1

1

2

Typ

B62-36G

A

Not-Ex-area
(control room)

optionally overvoltage arrester

Outer
isolation

Screen

Signal conditioning
instrument or safety
barrier

Cathodic corrosion protection
2 … 24 V (object voltage)

Note:

[A] Between control room and overvoltage

protection system a suitable cable, if
necessary with screen or metal cover, should
be used. Connect screen or metal cover - if
necessary - only to the electrode side of the
overvoltage protection system. With cathodic
corrosion protection the cable must be
provided with an outer isolation.

Ex-area

Electrode EK

External
earth
terminal

[1]

Vessel
Zone 0

Without cathodic corrosion protection: to
potential equalisation line

Electrical connection

Vessel with cathodic corrosion protection

E2

E1

A2

A1

A1

A2

E2

E1

1

2

Typ

B62-36G

Typ

B62-36G

B

A

Ex-area

Not-Ex-area
(control room)

optionally overvoltage arrester

Metal housing
mounted earth-free

optionally overvoltage arrester
B62 - 36 G Ex 0 (metal housing) or
B62 - 36 G Ex (plastic housing)
(L

i

= 0,15 mH, C

i

= 1,5 nF)

Electrode EK

Outer
isolation

Outer
isolation

Screen

Screen

Signal conditioning
instrument or safety
barrier

Earth / PA-connection
terminal

Cathodic corrosion protection
2 … 24 V (object voltage)

External
earth
terminal

Note:

[A] and [B] see "Vessel without cathodic corrosion protection“ on
the previous page.

min. 4 mm

2

Cu

Vessel
Zone 0

Capacitive electrode with integral overvoltage protection module

Vessel with/without cathodic corrosion protection