3 continuous level measurement – VEGA Capacitive electrodes EK … with signal conditioning instrument User Manual

Page 29

Advertising
background image

Capacitive electrodes EK with signal conditioning instrument

29

Set-up

4.3 Continuous level measurement

When you state the medium with your order, the oscillator of the electrode is already pread-
justed. In this case the medium is stated on the order confirmation.

• Choose with the changeover switch on the oscillator the stage according to the following

schedule.
Take the column corresponding to your medium and choose by means of the length of your
electrode the suitable range.
The stated lengths partly do not correspond to the actually available electrodes.
When the medium has a DK-value which is between the values stated in the table, the max.
permissible electrode length per measuring range must be averaged appropriately.
In case of larger lengths or when there is nothing else stated in the table, choose range 3.
If you are not sure, set the changeover switch always to the next higher stage.

Medium

Non-conductive

Non-conductive

Conductive

1)

EK-type

and DK = 2

and DK = 10

or DK > 50

EK 11

0 - 5,5 m

range 1

0 - 0,8 m

range 1

––

––

0,8 - 4,5 m

range 2

––

EK 11 with concentric tube

0 - 1,5 m

range 1

0 - 0,15 m

range 1

––

––

0,15 - 0,9 m

range 2

––

EK 18

0 - 6 m

range 1

0 - 1 m

range 1

––

––

1 - 5,5 m

range 2

––

EK 21 (2 mm-isolation)

0 - 5 m

range 1

0 - 1,1 m

range 1

0 - 0,25 m

range 1

––

1,1 - 6 m

range 2

0,25 - 1,4 m

range 2

EK 21 (2 mm-isolation)

0 - 2 m

range 1

0 - 0,5 m

range 1

0 - 0,3 m

range 1

with concentric tube

––

0,5 - 2,5 m

range 2

0,3 - 1,7 m

range 2

EK 21 (3,2 mm-isolation)

0 - 6 m

range 1

0 - 1,5 m

range 1

0 - 0,6 m

range 1

––

1,5 - 6 m

range 2

0,6 - 3 m

range 2

EK 21 (3,2 mm-isolation)

0 - 3,5 m

range 1

0 - 1 m

range 1

0 - 0, m

range 1

with concentric tube

––

1 - 5,5 m

range 2

0,7 - 4 m

range 2

EK 24

0 - 6 m

range 1

0 - 1 m

range 1

0 - 0,15 m

range 1

––

1 - 5,5 m

range 2

0,15 - 0,8 m

range 2

EK 24 with concentric tube

0 - 2 m

range 1

0 - 0,4 m

range 1

0 - 0,15 m

range 1

––

0,4 - 2 m

range 2

0,15 - 0,9 m

range 2

EK 26

0 - 6 m

range 1

0 - 1,5 m

range 1

0 - 0,5 m

range 1

––

1,5 - 6 m

range 2

0,5 - 2,8 m

range 2

EK 31

0 - 6 m

range 1

0 - 1 m

range 1

––

6 - 30 m

range 2

1 - 5 m

range 2

––

EK 42

0 - 9 m

range 1

0 - 2 m

range 1

0 - 0,8 m

range 1

9 - 30 m

range 2

2 - 10 m

range 2

0,8 - 4,5 m

range 2

1)

Oscillator E17 from a conductivity > 10 µS, oscillator E18 from a conductivity > 100 µS.