Capacitive electrodes EL 4 … 20 mA - Compact

22652-EN-020809

L

Fixing weight

Mounting

Lateral mounting

With measuring probes that deliver continuous
measured values, the electrode must be in-
stalled vertically. If installation from the top is
not possible, the electrodes can also be
mounted laterally (fig. 2.5).

Under accessories in our price list, you can
find a screening tube and a closing cone or an
angled rod electrode with which the instrument
can also be laterally mounted. Determine a
screening tube length (L) that will not allow
product bridges to form between cable and
vessel wall, and that will not allow the electrode
cable to touch the vessel wall. Use a fixing
weight or a fixing insulator.

Fig. 2.5 Continuous electrodes