Setup

Adjustment steps

On the following pages you will see the menu
schematic of the HART

®

handheld in conjunc-

tion with capacitive electrodes.
The most important adjustment steps are
marked in the menu schematic with the letters
A … D.

General information on the HART

®

handheld:

If you have entered or modified parameters,
you have to push the „

ENTER“ key. The ad-

justment is saved in the handheld, but not in
the sensor itself.

After you have pushed „

ENTER“, you have to

push „

SEND“ to transfer the settings to the

sensor.

After pushing „

SEND“, a warning is displayed.

If you push „

OK“, the setting is transferred to

the sensor.

In a further safety enquiry you are asked to
switch the system from manual to automatic
operation. Confirm with „

OK“.

With

„HOME“ you return to the initial menu.

Generic: SENSOR
PV LRV

0.000 m

10.000

HELP DEL ABORT ENTER

4.1

(5.1)

Empty adjustment without
medium

Generic: SENSOR

1 PV

LRV

2 PV

URV

HELP SEND

HOME

Generic: SENSOR

- WARNING-

Pressing ”OK“ will
change device output.

Put loop in manual

ABORT OK

Generic: SENSOR

- WARNING-

Return control loop to
automatic control.

OK

Generic: SENSOR

1 PV

LRV

2 PV

URV

HELP

HOME