Vessel with cathodic corr osion pr otection, Electrical connection, Ex) area zone1 non (ex) area – VEGA Capacitive electrodes EL 4 … 20 mA - Compact User Manual

Page 24

Advertising
background image

24

Capacitive electrodes EL 4 … 20 mA - Compact

22652-EN-020809

Electrical connection

A

B

2

1

E2

E1

A2
A1

2

1

A2

A1

E2
E1

V

essel with cathodic corr

osion pr

otection

(Ex) area Zone1

Non (Ex) area

Overvoltage
protection unit
mounted to
oscillator

Oscillator

b)Capacitive electrodes with external

overvoltage protection unit

Screen

Cathodic tank protection
2 … 24 V (object voltage)

CB
2-36

C A P
E32(H)EX

External ground terminal

Internal ground terminal

Vessel
Zone 0

Li, Ci of the oscillator with overvoltage
protection unit
Li = 0.27 mH
Ci = 8.5 nF

Control room
optionally:
Overvoltage
protection insert

Signal
condit-
ioning
instru-
ment
or
safety
bar-
rier

Type B62-36G

Li=0.15 mH
Ci=2.5 nF

Overvoltage protection unit

Overvoltage arrester in
metal housing or in plastic
housing must be installed
earth-free

External ground terminal

Internal ground terminal

Cathodic tank protection
2 … 24 V (object voltage)

Insulated cable
min. 4 mm

2

Vessel
Zone 0

Oscillator
Li=0.12 mH
Ci=6 nF

Screen

CAP
E32
(H)Ex

Type
B62-36G
Li=0.15 mH
Ci=2.5 nF

A suitable cable, if necessary with metal cover or
screen, must be used between control room and
overvoltage protection system. Metal cover or
screen - if necessary - should only be connected to
the electrode side of the overvoltage protection
system. The cable must have an outer insulation.
Test voltage of cable A: • 500 V AC

A suitable cable with metal cover, screen or a
suitable cable in a protective metal tube must be
used between overvoltage protection system and
capacitive electrode (metal cover or protective
tube must not be earthed)
Test voltage of cable B: • 1500 V AC

a) Capacitive electrodes with integrated
overvoltage protection unit type CB 2-36