.1 General instructions

N

ote the following points when selecting the installation

location.

l

S

ideways movements of the transmitter can cause

measurement errors

à Therefore, mount VEGAWELL 72 in a calm area or in a

suitable protective tube

Information:
W

e recommend the measuring instrument holder from the

VEGA

line of accessories (article no. BARMONT.B) for

fastening VEGAWELL 72.

l

T

he protective cover prevents mechanical damage to the

measuring cell. It should only be removed when the sensor
is deployed in extremely polluted water.

l

T

he connection cable has a capillary for atmospheric

pressure compensation

à Therefore lead the cable end into a dry space or directly

into a suitable terminal housing.

Information:
F

or this purpose, VEGA recommends VEGABOX 02. It

contains terminals and a filter element for pressure compen-
sation. A suitable protective cover is available for outdoor
mounting.

Mounting position

Pressure compensation

Mounting example