Fig. 6: Vessel with conical bottom
D
o not mount the instruments in or above the filling stream. Make sure
that you detect the product surface, not the inflowing product.
Fig. 7: Inflowing liquid
Flush mounting
T
he best way to mount the sensor, also with respect to cleanability, is
fl
ush on a block flange (flange without socket piece) or with hygienic
fi
ttings, e.g. Neumo Biocontrol.
Mounting on socket
Inflowing medium
Socket
VEGAPULS
63 • 4 … 20
mA/HART - two-wire
15
4 M
ounting