3 exchanging the electronics module – VEGA VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART - two-wire User Manual

Page 46

Advertising
background image

Error

Cause

Rectification

O

perating voltage

too low or load
resistance too
high

C

heck, adapt if necessary

C

urrent signal

greater than 22 mA
or less than
3.6

mA

E

lectronics mo-

dule in the sensor
defective

E

xchange the instrument or send it in

for repair

I

n Ex applications, the regulations for the wiring of intrinsically safe

circuits must be observed.

?

E

013

l

no measured value available

à Sensor in boot phase
à Sensor does not find an echo, e.g. due to faulty installation or

wrong parameter adjustment

?

E

017

l

A

djustment span too small

à Carry out a fresh adjustment and increase the distance

between min. and max. adjustment

?

E

036

l

no operable sensor software

à Carry out a software update or send instrument for repair

?

E

041, E042, E043

l

H

ardware error, electronics defective

à Exchange the instrument or send it in for repair

D

epending on the reason for the fault and the measures taken, the

steps described in chapter "Set up" may have to be carried out again.

8

.3 Exchanging the electronics module

I

f the electronics module is defective, it can be replaced by the user.

I

n Ex applications only one instrument and one electronics module with

respective Ex approval may be used.

I

f there is no electronics module available on site, one can be ordered

from the VEGA agency serving you.

T

he new electronics module must be loaded with the settings of the

sensor. These are the options:

Error messages via the
indicating and adjust-
ment module

Reaction after fault rec-
tification

Sensor serial number

46

VEGAPULS

63 • 4 … 20

mA/HART - two-wire

8 M

aintenance and fault rectification

28436

-EN

-120530

Advertising