VEGA VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART - two-wire User Manual

Page 36

Advertising
background image

Note:
C

heck the distance to the product surface, because if an incorrect (too

large) value is entered, the existing level will be saved as false signal.
T

he filling level would then no longer be detectable in this area.

T

he menu item "Extended setting" offers the possibility to optimise

VEGAPULS

63

for applications in which the level changes very

quickly. To do this, select the function "Quick level change > 1 m/min.".

E

xtended setting

quick level change > 1 m/min.

Note:
S

ince with the function "Quick level change > 1 m/min." the generation

of an average value of the signal processing is considerably reduced,
false reflections by agitators or vessel installations can cause
measured value fluctuations. A false echo memory is thus recom-
mended.

T

his function enables reading out parameter adjustment data as well

as writing parameter adjustment data into the sensor via the indicating
and adjustment module. A description of the function is available in the
operating instructions manual "Indicating and adjustment module".

T

he following data are read out or written with this function:

l

M

easured value presentation

l

O

peration

l

M

edium

l

I

nner diameter of the standpipe (with standpipe versions)

l

V

essel form

l

D

amping

l

L

inearisation curve

l

S

ensor-TAG

l

D

isplayed value

l

D

isplay unit

l

S

caling

l

C

urrent output

l

U

nit of measurement

l

L

anguage

T

he following safety-relevant data are not read out or written:

l

HART

mode

l

PIN

l

SIL

C

opy sensor data

C

opy sensor data?

Extended setting/Quick
level change

Copy sensor data

36

VEGAPULS

63 • 4 … 20

mA/HART - two-wire

6 S

et up with the indicating and adjustment module PLICSCOM

28436

-EN

-120530