2 parameter adjustment with pactware – VEGA VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART - two-wire User Manual

Page 43

Advertising
background image

N

ecessary components:

l

VEGAPULS

63

l

PC

with PACTware and suitable VEGA DTM

l

VEGACONNECT

l

P

ower supply unit or processing system

1

2

4

3

OPEN

TWIST

USB

LOCK

Fig. 32: Connecting the PC via HART to the signal cable

1

VEGAPULS 63

2

HART resistance 250 Ω (optional depending on processing)

3

Connection cable with 2 mm pins and terminals

4

Processing system/PLC/Voltage supply

N

ecessary components:

l

VEGAPULS

63

l

PC

with PACTware and suitable VEGA DTM

l

VEGACONNECT

l

HART

resistance approx. 250 Ω

l

P

ower supply unit or processing system

Note:
W

ith power supply units with integrated HART resistance (internal

resistance approx. 250 Ω), an additional external resistance is not
necessary. This applies, e. g. to the VEGA instruments VEGATRENN
149A, VEGADIS 371, VEGAMET 381. C

ommon Ex separators are

also usually equipped with a sufficient current limitation resistance. In
such cases, VEGACONNECT 4 can be connected parallel to the
4 … 20

mA cable.

7

.2 Parameter adjustment with PACTware

F

urther setup steps are described in the operating instructions manual

"

DTM Collection/PACTware" attached to each CD and which can also

be downloaded from our homepage. A detailed description is available
in the online help of PACTware and the VEGA DTMs.

Note:
K

eep in mind that for setup of VEGAPULS 63, DTM-Collection in the

actual version must be used.

VEGACONNECT via
HART

VEGAPULS

63 • 4 … 20

mA/HART - two-wire

43

7 S

et up with PACTware and other adjustment programs

28436

-EN

-120530