Electrical connection

Calculation of L

int

/C

int

of the cable:

L

int

(cable) = L

ext

(ia IIC circuit) – L

int

(pressure

transmitter) – L

int

(overvoltage protection)

= 0.5 mH – 0.2 mH - 0.13 mH

= 0.17 mH

C

int

(cable) = C

ext

(ia IIC circuit) – C

int

(pressure

transmitter) – C

int

(overvoltage protection)

= 56 nF – 11.2 nF - 1 nF

= 44.8 nF

Calculation of the cable length:

0.17 mH

I = –––––––––– • m = 262 m

0.65 µH

44.8 nF

I = ––––––––––– • m = 373 m

120 pF *

To be on the safe side, the cable length in this
example should not exceed a value of 250 m.