1 error codes – VEGA VEGADIF 34 … 51 User Manual

Page 58

Advertising
background image

58

VEGADIF 34 … 51

20094-EN-030731

Diagnostics

6.1 Error codes

If faults occur, VEGADIF outputs error codes. The bar graph on the display module indicates the
last valid measured value and keeps it flashing.

If several errors occur at the same time, the sequence of the indication depends on the priority
of the errors.

Code

Type

Reason and rectification

E101

Failure

Electrical instrument failure
- EEPROM check sum error

E102

Warning

Electronic instrument failure with pointer display
- carry out a reset (Code 7864), carry out a fresh adjustment

E103

Failure

Initialisation is running
- wait until the procedure is finished

E104

Warning

Sensor adjustment, calibration error, adjustment points too close together
- fresh adjustment of the sensor

E106

Failure

Upload/Download active
- wait until the procedure is finished

E110

Failure

Check sum error
- carry out a reset (Code 5140), error remains
- removal by service

E111

Failure

No connection to the sensor-EEPROM (when switching on)

E112

Failure

No connection to the sensor ADC (only ceramic sensors)

E113

Failure

Measurement error during pressure and temperature measurement

E114

Failure

Measurement error during temperature measurement, temperature sensor defective

E115

Failure

Sensor gauge pressure P+
- remains until gauge pressure disappears

E116

Failure

Download error
- restart download

E120

Failure

Sensor low pressure
- remains until low pressure disappears

E602

Warning

Not monotonously raising or falling vessel characteristics
- check the plausibility of the manually entered characteristics.

Volume increases with the level?

E604

Warning

Vessel characteristics consists of less than 2 index markers
- check the manually entered characteristics

E605

Failure

Manual linearisation curve incomplete
.

Enter the linearisation curve in mode „Level linear“ and choose
the mode „Characteristics“.

E610

Failure

Adjustment error, same pressure value for Low and High
- check the adjustment

E620

Warning

Signal current/Measured value not within the permitted range < 3.8 mA or > 20.5 mA