Set-up – VEGA VEGADIF 34 … 51 User Manual

Page 39

Advertising
background image

VEGADIF 34 … 51

39

20094-EN-030731

!

1

+

2

-

3

+

-

Electronics powered by a VEGA signal conditioning instrument

Ammeter for local testing

Transmitter
terminals

0/4 … 20 mA

U

Kl

U

S

DISBUS

U

K

4 … 20 mA

R

X

If the differential pressure transmitters are operated on a VEGA signal conditioning instrument,
you have to connect the sensor via a resistor acc. to the following chart (see next page) to the
signal conditioning instrument during the HART

®

adjustment. Together with the inner resistance

of the signal conditioning instrument, the resistance value of 250

required for the HART

®

instru-

ment is reached.

If the resistance of the processing system or the power supply is more than 250

, then no

„adjustment resistor“ required.

1

+

2

-

3

+

-

~

+

-

Set-up

Ammeter for local testing

analogue / digital indicat-
ing instrument

Transmitter
terminals

Power supply
(Ri < 250

)

4 … 20 mA

U

Kl

U

A

U

S

R

X

U

K

Electronics powered by a power supply unit

Note:

An ammeter for local testing of the output current can be connected between terminal 1 and its
tag. This measurement can be carried out during operation without interrupting the supply ca-
ble.