VEGA VEGABAR 64 Foundation Fieldbus User Manual

Page 57

Advertising
background image

Nominal range

Overload, max. pressure Overload, min. pressure

0 … 900 psi

2900 psi

0 psi

Reference conditions and actuating variables (similar to DIN EN 60770-1)

Reference conditions according to DIN EN 61298-1

-

Temperature

+15 … +25 °C (+59 … +77 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Determination of characteristics

Limit point adjustment according to IEC 61298-2

Characteristics

linear

Reference installation position

upright, diaphragm points downward

Influence of the installation position

< 0.2 mbar/20 Pa (0.003 psig)

Deviation determined according to the limit point method according to IEC 60770

11)

Applies to digital interfaces (HART, Profibus PA, Foundation Fieldbus) as well as to analogue
current output 4 … 20 mA. Specifications refer to the set span. Turn down (TD) is the relation
nominal measuring range/set span.

Deviation

-

Turn down 1 : 1 up to 5 : 1

< 0.075 %

-

Turn down > 5 : 1

< 0.015 % x TD

Deviation with absolutely flush process fittings EV, FT

-

Turn down 1 : 1 up to 5 : 1

< 0.05 %

-

Turn down > 5 : 1

< 0.01 % x TD

Deviation with absolute pressure measuring range 0.1 bar

-

Turn down 1 : 1 up to 5 : 1

< 0.25 % x TD

-

Turn down > 5 : 1

< 0.05 % x TD

Influence of the product or ambient temperature
Applies also to instruments with analogue 4 … 20 mA current output and refers to the set span.

Thermal change zero signal and output span, reference temperature 20 °C (68 °F):

-

In the compensated temperature range
0 … +100 °C (+32 … +212 °F)

< (0.05 % + 0.1 % x TD)

-

Outside the compensated temperature
range

< (0.05 % + 0.15 % x TD)

11)

Incl. non-linearity, hysteresis and non-repeatability.

VEGABAR

64 • Foundation Fieldbus

57

10 Supplement