3 transfer of measured value, 1 format for transfer of measured value – VEGA VEGASCAN 850 Profibus DP signal output User Manual

Page 7

Advertising
background image

Profibus DP signal output VEGASCAN 850

7

Transfer of measured value

3 Transfer of measured value

The VEGASCAN DP-Gateway is configured
as DP-Normslave either with 50 byte consist-
ent input data and 2 byte consistent output
data with 6 byte consistent input data and 6
byte consistent output data. The DP master
transmits control information via the outputs
to VEGASCAN, to which VEGASCAN an-
swers respectively, outputting the data as
input information to the DP master.

3.1 Format for transfer of measured

value

Measured values and PC/DCS values

The measured values of the measurement
loops created on VEGASCAN are imaged
according to the way described in chapter
"2 PC/DCS output in VEGASCAN“ to the input
bytes of the Profibus master. They are avail-
able in VEGASCAN as so-called PC/DCS
values for collection.
A PC/DCS value consists of 6 bytes.

Structure of a measured value

Measured values of VEGASCAN consist of 2
bytes signed data. This means that the value
range comprises max. +32768 to -32767.

Structure of a PC/DCS value

A single PC/DCS value in VEGASCAN con-
sists of 6 bytes and is composed as follows.

PC/DCS value

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Add. info

High-Word

Low-Word

Measured value

Index

Status

high

low

high

low

The real measured value is in the low word of
the measured value and has a length of 2
bytes and is signed, this means that the
value range is +32768 to -32767.
The 2 bytes of the high word of the measured
value are actually not used, they are filled
with the value zero.

In addition to the PC/measured value,
VEGASCAN provides one byte per DCS
value for the PC/DCS index and another byte
for information on the actual status of the
measured value.

The PC/DCS output number is transmitted in
the byte index. The status describes the
condition of the respective measured value.
The content of the measured value is only
valid if the respective status has the value
zero.

If a status value unequal zero is returned, the
status value and the respective value in the
measured value field must be taken into
consideration for a detailed error diagnosis.
The following list explains possible errors:

Status Meas. value

Meaning

0x00

0xXXXX

valid measured value

0x80

0xXXXX

old meas. value (pro-
bably connection inter-
rupted)

0xFE

0x0000

no measured value
available (not config-
ured)

0xFF

0xFFFF

no VEGASCAN con-
nected

0xFF

0x00XX

Error information of a
single measurement
loop

XX = Error type

0xFF

0x8000

Error information of a
single measurement
loop
Error type is not defined

Advertising