VEGAMET 407 Z

Parameter adjustment

Empty, full adjustment in %

The measurement range for level 0 % and 100 % is
defined via the adjustment procedure.

When the vessel is partly filled or emptied the pro-
gramming is as described on the right, however
with previously determined %-values.
The min. measuring range must correspond to a
current

of > 300

µ

A.

Example

Full

• fill vessel

adjustment

• select mode in MODEFIELD
• program level 100 % in

PARAMETER FIELD

• then store with STO

Empty

• empty vessel

adjustment

• select mode in MODEFIELD
• program level 0 % in

PARAMETER FIELD

• then store with STO

The empty and full adjustments may be performed
in any order.

%

100

0 %

Vessel full

Vessel empty

50

Empty, full adjustment in mA

The measuring current values are coordinated to
the levels 0 % and 100 % with the adjustment.

The measuring currents are experience values or
can be taken from the attached test certificate.

The procedure is used:
- for adjustment without rate of product level

change

- for correction of previous adjustments (alarm E3

or E4)

- for adjustment without connection of a capacitive

electrode or a pressure transmitter (alarm E2)

Example

Full

• select mode in MODEFIELD

adjustment

• push button + and button MOD

simultaneously (data input for mA)

• program 18,75 mA in

PARAMETER FIELD

• then store with STO

Empty

• select mode in MODEFIELD

adjustment

• push button + and button MOD

simultaneously (data input for mA)

• program 5,28 mA in

PARAMETER FIELD

• then store with STO

The empty and full adjustments may be performed
in any order.

%

100

0

mA
18,75

5,28

Level 100 %
^ measuring current
18,75 mA

Level 0 % ^

measuring current
5,28 mA

50