VEGAMET 407 Z

Parameter adjustment

Password

All parameters can be interrogated as previously
described and their data indicated on the display.

Data input can be inhibited by programming the
password.

Alarm signals

Indication

Reason

Result

Measuring results

< - 10 %

Input below minimum limit (flashing)

without fail safe

> 110 %

Input above maximum limit (flashing)

Error code

E1

Connection cables reversed on

with fail safe

short-circuit

E2

Line break

E3

Incomplete or incorrect adjustm. proced.

E4

(together with flashing mode segments)

E8.1 …

Fault during

Current output = 22 mA

E8.4

data transfer (acc. to STO)

Voltage output
= 11 V or 5,5 V

E9

Fault in the EEPROM-memory

Activate password ....................................................

• select mode - - - - in MODEFIELD
• program figure 1 in PARAMETER FIELD
• then store with button STO

Adjust password .......................................................

• select the mode required for parameter adjust-

ment in the MODEFIELD, in the example mode t

• select data input, the keyword

0 - -

0

is displayed

in the PARAMETER FIELD

• program

0407

as password

• then store with button STO
• the parameter adjustment of e.g. mode t can be

made

(fail safe)