VEGAMET 407 Z

Alarm information

E1

E2

1

2

+

-

VEGAMET 407 Z

V

mA

4 … 20

12 … 24

2

1

2

1

Sensors

Measuring line

Capacitive

Pressure

measuring

transmitter

electrode

Fault diagnosis related to E1 or E2

Signal conditioning
instrument

Short-circuit

current > 22 mA

Check all connections

and measuring lines

Yes

No

Yes

No

Yes

No

Yes

No

Yes

No

Yes

No

Short-

circuit

removed

?

Short-

circuit

removed

?

Short-

circuit

removed

?

Sensor defect

Short-circuit in the

connection cable

Separate sensor from

connection cable

Separate signal conditionining

instrument from connection cable

Line break

current < 2 mA

Check supply voltage

and measuring line

Signal conditioning

instrument defect

approx.

24 V

?

Alarm

E1 dis-

played?

Alarm

E1 is

displayed

?

Auswertgerät defekt

Fault or break on the

sensor (capacitive

measuring electrode or

pressure transmitter)

Cable break

Short-circuit the signal conditioning

instrument terminals

Remove short-circuit of the terminals on the

signal conditioning instrument, then short-

circuit terminal 1 and 2 on the sensor

Signal conditioning

instrument defect

E1 extinguishes

Signal conditioning

instrument defect