VEGA VEGAMET 407 Z User Manual

Page 12

Advertising
background image

12

VEGAMET 407 Z

Effects

within the measuring range

outside the measuring range

-10 % … 0 % ...............100 % … 110 %

< -10 %

or >110 %

0/4 mA...............20 mA

22 mA

0 V..................10 V

11 V

0 V....................5 V

5,5 V

Example to end simulation ......................................

• push MOD–button again

Effects

- Cancel the simulated output values
- Transmits the true output values

Parameter adjustment

Integration time

Application
- Where the product surface is agitated the system

outputs may be stabilized by adjusting the inte-
gration time.

Important notes:
The integration time depends on the filling and
emptying period of the vessel, i.e. integration time

filling / emptying time. Mis-adjustment of the

integration time may degrade output sensitivity.

Definitions
- range = 0 … 199 sec.
- (0 … 199 secs. corresponds to the definition in

sec.)
At 200 sec. effects a time period, the actual value
is approx. 45 minutes.

- settings > 200 sec. are automatically limited to

the max. value 200 sec.

Example
- integration time of e.g. 15 sec.

• select mode t in MODEFIELD
• program 15 sec. in PARAMETER FIELD
• then store with STO

Example ..............to activate the simulation ………

• select mode SIM in MODEFIELD
• activate the simulation with button MOD
• increase or reduce the output with button + or

button –

t

Simulation mode

In the simulation mode it is possible to test the
measuring system over the whole measuring range
independent of the process.

Button + increases and
button – reduces
all output values.

The longer the simulation button + and – are
pressed the greater the rate of change.

Integration time is ignored during the simulation
sequence.

t

fault-monitoring-LED

lights

fault-monitoring relay

de-energizes

Advertising