Help for fault diagnosis

The measuring current stored during empty and full
adjustment can be displayed in the mode range by
pushing the plus-button.

Application with ……………………

-

inaccurate measurements or

-

alarm E3 or E4

Example:

Measuring current of the previous
adjustment related to 0 %

• select mode in MODEFIELD
• push plus-button, the adjustment current related

to 0 %, is displayed in PARAMETER FIELD

• reset by pushing the MOD-button twice

Measuring current of the previous
adjustment related to 100 %

• select mode in MODEFIELD
• push plus-button, the adjustment current related

to 100 %, is displayed in PARAMETER FIELD

• reset by pushing the MOD-button twice

Alarm information

E3

E4

=

Adjustment had been carried with no or with too
small level change.

=

The modes or %-values had been exchanged
during adjustment

or

Fault diagnosis related to E3

Fault diagnosis related to E4

Alarm

removed

?

Repeat the adjustment

(e.g. empty adjustment)

Repeat the 2nd part of the

adjustment (e.g. full

adjustment)

or carry out

adjustment in mA

see page 11

E3 or E4 and mode
segment extinguish

E3 or E4 and

mode segment extinguish

Note
- %-value and
- mode

Note:
min. measuring
distance; %-
value and mode