2 instructions for installation – VEGA VEGASWING 51 - contactless electronic switch User Manual

Page 12

Advertising
background image

Do not hold VEGASWING 51 on the tuning fork.

The process fitting must be sealed if there is gauge or low pressure in
the vessel. Before use, check if the seal material is resistant against
the measured product and the process temperature.

The max. permissible pressure is specified in chapter "Technical data"
or on the type label of the sensor.

The vibrating level switch is a measuring instrument and must be
treated accordingly. Bending the vibrating element will destroy the
instrument.

Warning:
The housing must not be used to screw the instrument in! Applying
tightening force can damage internal parts of the housing.

Use the hexagon above the thread for screwing in.

4

.2 Instructions for installation

For welded socket with O-ring in front and welding marking.

VEGASWING

51 has a defined thread runout. This means that every

VEGASWING

51 is in the same position after being screwed in.

Remove therefore the supplied flat seal from the thread of
VEGASWING

51. This flat seal is not required when using a welded

socket with front-flush seal.

Before welding, unscrew VEGASWING 51 and remove the rubber ring
from the welded socket.

The welded socket is provided with a marking (notch). For horizontal
mounting, weld the socket with the notch facing upward or downward;
in pipelines (DN 32 to DN 50) aligned with the direction of flow.

1

Fig. 5: Marking on the welded socket

1

Marking

Transport

Pressure/Vacuum

Handling

Welded socket

12